CAN/ULC-S PERIODIC INSPECTIONS AND TEST – DAILY AND MONTHLY. NOTE: Refer to Appendix D for examples of Inspection and Test Record. SCOPE. This Standard provides requirements for the inspection and testing of fire alarm systems and specifies the devices and functions to be inspected. 1 SCOPE This Standard prescribes requirements for the inspection and testing of fire alarm systems and specifies the devices and functions.

Author: Kagarr Mikamuro
Country: Bahrain
Language: English (Spanish)
Genre: Technology
Published (Last): 21 February 2004
Pages: 331
PDF File Size: 1.41 Mb
ePub File Size: 14.44 Mb
ISBN: 752-9-68561-397-4
Downloads: 35853
Price: Free* [*Free Regsitration Required]
Uploader: Samusar

Tamper switches inspected covers secured, leaks or corrosion? Main Power supply failure trouble signal operates. Valve handles in place? Switches for ancillary functions operate as per design and specification. Test circuit breakers and fuses for proper operation?

No missing or damaged pipe support devices? When sufficient particles accumulate, the unit hlc into an alarm condition.

Door holders and releases you, as the building owner, should know the difference and how they operate acn a fire alarm activation ; Elevator recall functions general alarm homing, alternate floor homing, and machine room and shaft fire operation ; Smoke control functions electrically operated dampers, fans, pressurization fans, etc.

  AIA A701 PDF

Ground fault tested on positive and negative initiates trouble signal. Alarm device, test on dry pipe, pre-action or deluge system using bypass?

CAN/ULC-S536-04 Fire Alarm Annual Inspection Test Form

Free from mildew, cuts and deterioration? Description of alarm signal operation. Jockey pump operational and in good condition? The fire alarm system documentation is on site and includes a description of ss536 system.

H Operation of voice paging does not interfere with initial inhibit time of alert I signal and alarm signal. Backflow prevention assembly shall be tested at the design flow. S Input circuit supervision fault causes a trouble indication. Visible signaling appliances tested? Dry-pipe full flow trip test to be done every 3rd year: L Inspected for electrolyte leakage.

CAN/ULC-S | Standards Council of Canada – Conseil canadien des normes

Individual alarm and supervisory zone indication operates. Correct battery rating as determined by battery calculations based on full system z536. Have modifications or renovations been done since the last inspection? Reconnect ancillary functions off site connections?

Direct Connection yes no Number of Conventional Zones: Ss536, including press to talk switch, operates. Low temperature supervisory device tested. Trouble signal on the voice communication system results in common trouble signal on the fire alarm system. Multi-line sequential display operates as per Appendix W536.

  2007 HONDA ACCORD MANUAL PDF

Extinguishing system controlled by fire alarm system? Main drain test shall be conducted on each system riser. Backflow prevention assemblies shall be inspected locked or properly supervised by an acceptable electrical means.

Fire Alarm System Periodic Inspection (CAN/ULC-S)

Sprinklers and spray nozzles protecting commercial cooking equipment and ventilating systems replaced except for bulbtype which show no sign of grease buildup? Identify active field device and supporting field device, data communication link DCLaddress and location.

For reduced voltage or reduced current starting, record time controller is on first step: Hydrostatic test at not less than A security or fire alarm system that employs integrated smoke detectors is by far the best way to protect your family or workers. Manual transfer from alert signal to alarm signal. Record the date, revision and version of firmware: Manual activation devices passed test?

Pipe and fittings shall be inspected from floor level? Reduced pressure assembly valves inspected for leaks or corrosion? Yes No Time for motor to accelerate to full speed: